1704.1 General
Special inspections and tests, statements of special inspections, responsibilities of contractors, submittals to the building official and structural
observations shall meet the applicable requirements of this section.
1704.2 Special Inspections and Tests
Where application is made to the building official for construction as specified in Section 105, the owner or the owner’s authorized agent, other
than the contractor, shall employ one or more approved agencies to provide special inspections and tests during construction on the types of
work specified in Section 1705 and identify the approved agencies to the building official. These special inspections and tests are in addition to
the inspections by the building official that are identified in Section 110.
Exceptions:
- Special inspections and tests are not required for construction of a minor nature or as warranted by conditions in the
jurisdiction as approved by the building official. - Unless otherwise required by the building official, special inspections and tests are not required for Group U occupancies that
are accessory to a residential occupancy including, but not limited to, those listed in Section 312.1. - Special inspections and tests are not required for portions of structures designed and constructed in accordance with the coldformed steel light-frame construction provisions of Section 2211.1.2 or the conventional light-frame construction provisions of
Section 2308. - The contractor is permitted to employ the approved agencies where the contractor is also the owner.
1704.2.1 Special Inspector Qualifications
Prior to the start of the construction, the approved agencies shall provide written documentation to the building official demonstrating the
competence and relevant experience or training of the special inspectors who will perform the special inspections and tests during
construction. Experience or training shall be considered to be relevant where the documented experience or training is related in
complexity to the same type of special inspection or testing activities for projects of similar complexity and material qualities. These
qualifications are in addition to qualifications specified in other sections of this code.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act
as the approved agency and their personnel are permitted to act as special inspectors for the work designed by them, provided they qualify
as special inspectors.
1704.2.2 Access for Special Inspection
The construction or work for which special inspection or testing is required shall remain accessible and exposed for special inspection or
testing purposes until completion of the required special inspections or tests.
1704.2.3 Statement of Special Inspections
The applicant shall submit a statement of special inspections in accordance with Section 107.1 as a condition for permit issuance. This
statement shall be in accordance with Section 1704.3.
Exception: A statement of special inspections is not required for portions of structures designed and constructed in accordance with the
cold-formed steel light-frame construction provisions of Section 2211.1.2 or the conventional light-frame construction provisions of
Section 2308.
1704.2.4 Report Requirement
Approved agencies shall keep records of special inspections and tests. The approved agency shall submit reports of special inspections
and tests to the building official and to the registered design professional in responsible charge. Reports shall indicate that work inspected
or tested was or was not completed in conformance to approved construction documents. Discrepancies shall be brought to the immediate
attention of the contractor for correction. If they are not corrected, the discrepancies shall be brought to the attention of the building official
and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting
required special inspections and tests, and correction of any discrepancies noted in the inspections or tests, shall be submitted at a point in
time agreed upon prior to the start of work by the owner or the owner’s authorized agent to the building official.
1704.2.5 Special Inspection of Fabricated Items
Where fabrication of structural, load-bearing or lateral load-resisting members or assemblies is being conducted on the premises of a
fabricator’s shop, special inspections of the fabricated items shall be performed during fabrication, except where the fabricator has been
approved to perform work without special inspections in accordance with Section 1704.2.5.1.
1704.2.5.1 Fabricator Approval
Special inspections during fabrication are not required where the work is done on the premises of a fabricator approved to perform such
work without special inspection. Approval shall be based on review of the fabricator’s written fabrication procedures and quality control
manuals that provide a basis for control of materials and workmanship, with periodic auditing of fabrication and quality control practices
by an approved agency or the building official. At completion of fabrication, the approved fabricator shall submit a certificate of
compliance to the owner or the owner’s authorized agent for submittal to the building official as specified in Section 1704.5 stating that
the work was performed in accordance with the approved construction documents.
1704.3 Statement of Special Inspections
Where special inspections or tests are required by Section 1705, the registered design professional in responsible charge shall prepare a
statement of special inspections in accordance with Section 1704.3.1 for submittal by the applicant in accordance with Section 1704.2.3.
Exception: The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for
construction not designed by a registered design professional.
1704.3.1 Content of Statement of Special Inspections
The statement of special inspections shall identify the following: - The materials, systems, components and work required to have special inspections or tests by the building official or by the
registered design professional responsible for each portion of the work. - The type and extent of each special inspection.
- The type and extent of each test.
- Additional requirements for special inspections or tests for seismic or wind resistance as specified in Sections 1705.11,
1705.12 and 1705.13. - For each type of special inspection, identification as to whether it will be continuous special inspection, periodic special
inspection or performed in accordance with the notation used in the referenced standard where the inspections are defined.
1704.3.2 Seismic Requirements in the Statement of Special Inspections
Where Section 1705.12 or 1705.13 specifies special inspections or tests for seismic resistance, the statement of special inspections shall
identify the designated seismic systems and seismic force-resisting systems that are subject to the special inspections or tests.
1704.3.3 Wind Requirements in the Statement of Special Inspections
Where Section 1705.11 specifies special inspection for wind resistance, the statement of special inspections shall identify the main
windforce-resisting systems and wind-resisting components that are subject to special inspections.
1704.4 Contractor Responsibility
Each contractor responsible for the construction of a main wind- or seismic force-resisting system, designated seismic system or a wind- or
seismic force-resisting component listed in the statement of special inspections shall submit a written statement of responsibility to the building
official and the owner or the owner’s authorized agent prior to the commencement of work on the system or component. The contractor’s
statement of responsibility shall contain acknowledgement of awareness of the special requirements contained in the statement of special
inspections.
1704.5 Submittals to the Building Official
In addition to the submittal of reports of special inspections and tests in accordance with Section 1704.2.4, reports and certificates shall be
submitted by the owner or the owner’s authorized agent to the building official for each of the following: - Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting members or assemblies on the
premises of an approved fabricator in accordance with Section 1704.2.5.1. - Certificates of compliance for the seismic qualification of nonstructural components, supports and attachments in accordance with
Section 1705.13.2. - Certificates of compliance for designated seismic systems in accordance with Section 1705.13.3.
- Reports of preconstruction tests for shotcrete in accordance with Section 1908.5.
- Certificates of compliance for open web steel joists and joist girders in accordance with Section 2207.5.
- Reports of material properties verifying compliance with the requirements of AWS D1.4 for weldability as specified in Section
26.6.4 of ACI 318 for reinforcing bars in concrete complying with a standard other than ASTM A706 that are to be welded. - Reports of mill tests in accordance with Section 20.2.2.5 of ACI 318 for reinforcing bars complying with ASTM A615 and used to
resist earthquake-induced flexural or axial forces in the special moment frames, special structural walls or coupling beams
connecting special structural walls of seismic force-resisting systems in structures assigned to Seismic Design Category B, C, D,
E or F.
1704.6 Structural Observations
Where required by the provisions of Section 1704.6.1, 1704.6.2 or 1704.6.3, the owner or the owner’s authorized agent shall employ a
registered design professional to perform structural observations. Structural observation does not include or waive the responsibility for the
inspections in Section 110 or the special inspections in Section 1705 or other sections of this code.
Prior to the commencement of observations, the structural observer shall submit to the building official a written statement identifying the
frequency and extent of structural observations.
At the conclusion of the work included in the permit, the structural observer shall submit to the building official a written statement that the site
visits have been made and identify any reported deficiencies that, to the best of the structural observer’s knowledge, have not been resolved.
1704.6.1 Structural Observations for Structures
Structural observations shall be provided for those structures where one or more of the following conditions exist: - The structure is classified as Risk Category IV.
- The structure is a high-rise building.
- Such observation is required by the registered design professional responsible for the structural design.
- Such observation is specifically required by the building official.
1704.6.2 Structural Observations for Seismic Resistance
Structural observations shall be provided for those structures assigned to Seismic Design Category D, E or F where one or more of the
following conditions exist: - The structure is classified as Risk Category III or IV.
- The structure is assigned to Seismic Design Category E, is classified as Risk Category I or II, and is greater than two stories
above the grade plane.
1704.6.3 Structural Observations for Wind Resistance
Structural observations shall be provided for those structures sited where V is 130 mph (58 m/sec) or greater and the structure is classified
as Risk Category III or IV.